Products Intelligent Fire Alarm System Addressable MCP, Sounder Strobe, Modules & Repeter Details
DetailsIntelligent Input Module:CFT-952
概述
The CFT-952 Intelligent input module (CFT-952 module for short) is used with CFT-MN300,a two-bus fire alarm control panel. It can be connected with a conventional smoke detector, a conventional heat detector, a conventional manual call point, a conventional hooter/horn and some other equipment. After the said equipment starts to operate, the alarm signal output will be sent by the CFT-952 module to the fire alarm control panel through a signal bus to give a fire alarm. 性能特点
Mode of operation: Nonpolar two-wire system
2. Quiescent current: <0.5mA (bus); <6mA (power line)
3. Action current: <2mA (bus); <15mA (power line)
4. Operation indicator: The inspection indicator will blink once about every 12 seconds
in the inspection status or remain lit in the operation status.
5. Operating environment: Temperature: -10℃~50℃; relative humidity: ≤95% (40℃±2℃, without condensation)
6. Terminal load: 4.7K resistance
7. External dimensions: 86×86×40(mm)
View: 5163