Products Intelligent Fire Alarm System Addressable MCP, Sounder Strobe, Modules & Repeter Details
DetailsIntelligent Input/Output Module:CFT-956
概述
The CFT-956 Intelligent Input/Output Module(CFT-956 module for short) is used with CFT-MN300,a two-bus linkage fire alarm control panel. It is mainly used to realize an output control for fire linkage equipment (such as smoke dampers, blow valves and fire dampers) and receive the feedback signals of the fire linkage equipment so that a judgment on whether or not the fire linkage equipment is operating normally can be done.
性能特点
Mode of operation: Nonpolar two-wire system
2. Quiescent current: <0.6mA (power-down mode)
3. Action current: <10mA
4. Capacity of the output control contact: 2A@DC30V
5. Operation indicator: The inspection indicator will blink once about every 12 seconds
in the inspection status or remain lit in the output status; the input indicator will remain lit in the feedback status.
6. Operating environment: Temperature: -10℃~50℃; relative humidity: ≤95% (40℃±2℃, without condensation)
7. Terminal load: 47K resistance