Detailed introduction of installation of independent temperature fire detection alarm

Time: 2020-04-26 View: 2914
1743/5000 
Operating instruction

Please read this manual carefully before use to ensure proper installation and use

An overview,

Independent temperature-sensitive fire detection alarm (hereinafter referred to as the alarm) can detect when the fire site temperature rise, timely alarm signal, suitable for air volume and dust too much and not suitable for the installation of smoke detection alarm. The alarm adopts temperature sensing devices and excellent production technology, stable work, beautiful appearance, simple installation, no need for debugging, can be widely used in hotels, stores, Internet cafes, dance halls, cafes, leisure halls, residential and other places for fire safety monitoring. The buzzer is built in to make a strong sound after the alarm. The alarm is powered by 9V cascade battery, which consumes very little power and can last for more than a year.

2. Characteristics and technical indicators

1. Power supply: DC9V battery

2. Indicator light: red.

3. Alarm temperature: 58℃±3℃

4. Alarm sounds > 85dB

5. Protection area: > 40m2 specific parameters shall be subject to the design specification for automatic fire alarm system (GB 50116)

6. Operating environment: temperature: -10℃ ~ +55℃, relative humidity ≤95%, no condensation

7. Service life: 5 years of BBB 0

8. Overall size: 105mm in diameter, 59mm in height (with base)

9. Shell material and color: ABS porcelain white

10. Mounting hole spacing: 60mm

11. Meet the standard: gb4716-2005

The main function of alarm

1 alarm test function: the alarm can work normally after being connected to the battery, and the indicator light will flash once about 8 seconds. Press the test button, the buzzer will sound the alarm, and the indicator light will shine. Release the test button and the alarm will work normally.

2 alarm function: when the temperature around the alarm reaches the alarm temperature threshold, the indicator light will flash quickly and the alarm will sound. When the temperature drops, the alarm can be automatically restored. Under the alarm state, press the test button to mute the alarm.
3. Power undervoltage warning function: the alarm has the function of battery voltage detection. When the power supply battery voltage is lower than 7V, the alarm will emit a short "beep" sound and light indication at the same time.

Alarm function debugging

The detector must be tested after installation or after each regular maintenance.

During the test, use a hot blower to blow against the thermistor from 15CM away from the detector until the detector alarms (make sure the lamp is always on). Do not use open fire direct baking detector to avoid burning the detector or fire.
Limitations of alarms

The alarm will not work when there is no electricity. The alarm is battery-powered and will not alarm if there is no battery, the battery power is exhausted or the battery is installed incorrectly.

3. Fault analysis and troubleshooting

1. Call the police when the power is on

§ make sure the alarm is not loose due to falling or bumping during transportation or dump.

§ if the above two conditions are excluded, the alarm still does not work properly, please return the alarm for maintenance.


2. Press the test button without warning

§ check whether there is bad contact between the battery and the battery buckle. If the connection is not good, please fasten the two.

§ check whether the battery has sufficient power and can be verified by replacing it with a new battery;


§ if not, please return the alarm for maintenance.


Repair and maintenance

1. After the alarm is installed and put into use, press the test button to test the alarm every week. If any fault is found, please contact the local dealer for technical support or repair.

2. Under normal conditions, the service life of the battery is about one year, but harsh conditions such as high temperature and high humidity will shorten the service time; When the alarm report battery undervoltage fault, please replace the battery in time.

Three, installation,

1. Installation location

1) suitable installation location


The best position for the alarm should be in the middle of the roof, where the alarm is closest to each part of the room.

When installed on the roof: the edge of the alarm should be at least 50cm away from any wall.

When mounted on a sloping or humanoid roof: the alarm should be kept at a distance from the roof. When the slope is less than 30°, the distance of 0.2m is appropriate, and that of 0.3m ~ 0.5m is appropriate if it is greater than 30°.

2. Installation method

Note: do not install alarms in new buildings until the decoration and other processes that may produce dust have been completed and the rooms have been cleaned.

1) inspection: before installation, it is necessary to check whether the alarm housing is intact and whether the identification is complete.

2) installation

Warning: alarms must be installed in accordance with local electrical installation regulations. Failure to comply with these regulations may result in loss of life and property.

* make two installation holes on the ceiling 60mm apart, and fix the base of the alarm with expansion plug and self-tapping screw, as shown in figure 3.

* turn the alarm counterclockwise, remove the base, press the 9V stacked battery according to the polarity mark of the battery buckle, press the battery tightly, then press the battery buckle line and the battery into the battery compartment at the bottom of the alarm.

* turn the alarm clockwise on the base and fasten it in place.

Vii. Warning:

* do not test alarms with any open flame. This can ignite and damage alarms and even cause a fire.